IoT and Automation

Line-M-4IO-RV

Expansion modules

Code: D73004

Protocol: Modbus/RTU
Communications: Bus-Line
Nº relays: 4
Digital inputs: 4 (230 V)
Download Datasheet

Overview

Module with 4 230V relay inputs and outputs.

The expansion modules of the Line range provide a simple way to extend the features of any version of the line-ED-Cloud or line-EDS-PS, and of the line-CVM-D32 network analyser.

They allow adding digital outputs and inputs, analogue inputs and outputs or any combination thereof, to the devices.

The modules are connected laterally and are detected automatically when the lateral connection is made, which greatly simplifies the installation and configuration of the modules.

Technical Specifications

DC power supply

Line-M-4IO-RV DC power supply
Consumptionmax. 2 W

Voltage measurement circuit

Line-M-4IO-RV Voltage measurement circuit
Input impedance140 kΩ

Digital relay outputs

Line-M-4IO-RV Digital relay outputs
TypeClass A, high frequency current filtering
Quantity4
Maximum open contact voltage250 V ~
Maximum current6 A ~
Mechanical life5 × 10⁶ cycles
Maximum switching capacity1500 VA

Digital inputs

Line-M-4IO-RV Digital inputs
Quantity4
Input/output insulation3.75 kV ~
Maximum short-circuit current50 mA
Operating voltage230 V ~
Minimum signal width10 ms

User interface

Line-M-4IO-RV User interface
LED9 LEDs

Environmental characteristics

Line-M-4IO-RV Environmental characteristics
Working temperature-10 … +50 °C
Storage temperature-20 … +70 °C
Relative humidity (without condensation)5 … 95%
Protection classIP30, Front: IP40

Mechanical characteristics

Line-M-4IO-RV Mechanical characteristics
EnvelopeSelf-extinguishing V0 plastic
FasteningDIN rail (IEC 60715)
Weight (kg)0,178
Size (width × height × depth)52.5 × 118 × 70 mm

Standards

Line-M-4IO-RV Standards
StandardsUNE-EN 61010-1, UNE-EN 61000-6-2, UNE-EN 61000-6-4
Electrical safety, Installation categoryCAT III 300 V
Electrical safety, Maximum height (m)2000

Applications

Expansion of inputs/outputs from line-CVM-D32 or line-EDS network analysers.

Alarms can be programmed independently based on high/low values, hysteresis, timer on/off delays, normally open or closed rest state and interlocks.

Track the status of components in the installation by using the status of the inputs to the module with network voltages of up to 230V~

Management of up to 4 tariffs with activation of the different inputs to the module.