IoT and Automation

Line-M-8I6O

Expansion modules

Code: D73008

Protocol: Modbus/RTU
Communications: Bus-Line
Nº relays: 6
Digital inputs: 8
Download Datasheet

Overview

Module with 8 inputs and 6 outputs floating relay.

The expansion modules of the Line range provide a simple way to extend the features of any version of line-EDS-Cloud, line-EDS-PS.

They allow adding digital outputs and inputs, analogue inputs and outputs or any combination thereof, to the devices.

The modules are connected laterally and are detected automatically when the lateral connection is made, which greatly simplifies the installation and configuration of the modules.

Technical Specifications

DC power supply

Line-M-8I6O DC power supply
Consumptionmax. 4 W

Voltage measurement circuit

Line-M-8I6O Voltage measurement circuit
Input impedance3 kΩ

Digital relay outputs

Line-M-8I6O Digital relay outputs
TypeClass A, high frequency current filtering
Quantity6
Maximum open contact voltage250 V ~ / 30 Vdc
Maximum current5 A ~
Mechanical life5 × 10⁶ cycles
Maximum switching capacity1250 VA / 150 W

Digital inputs

Line-M-8I6O Digital inputs
Quantity8
TypeOptocoupler
Input/output insulation3.75 kV ~
Minimum signal width10 ms

User interface

Line-M-8I6O User interface
LED15 LEDs

Environmental characteristics

Line-M-8I6O Environmental characteristics
Working temperature-10 … +50 °C
Storage temperature-20 … +70 °C
Relative humidity (without condensation)5 … 95%
Protection classIP30, Front: IP40 / IK08

Mechanical characteristics

Line-M-8I6O Mechanical characteristics
EnvelopeSelf-extinguishing V0 plastic
FasteningDIN rail
Weight (kg)0,242
Size (width × height × depth)52.5 × 118 × 70 mm

Standards

Line-M-8I6O Standards
StandardsUNE-EN 61010-1, UNE-EN 61000-6-2, UNE-EN 61000-6-4
Electrical safety, Installation categoryCAT III 300 V
Electrical safety, Maximum height (m)2000

Applications

Expansion of inputs/outputs from line-EDS network analysers.

Alarms can be programmed independently based on high/low values, hysteresis, timer on/off delays, normally open or closed rest state and interlocks.

Track the status of components in the installation by using the status of the inputs to the module.