IoT and Automation

RS2RS

Converter RS-232/RS-485 converter and RS-485/RS-485 amplifier

Code: D80310

Download Datasheet

Overview

The RS2RS converter lets you connect units with RS-232 communications to a RS-485 network. It also works as a repeater or amplifier of RS-485 networks. The converter is designed to be used in industrial environments, thanks to its galvanic insulation.It automatically adapts to all half-duplex communications protocols without the need to modify the software. It works as a communications transducer between RS-232/RS-485 data buses or as an octocoupled RS-485/RS-485 amplifier. The RS2RS automatically switches between transmission (Tx) and reception (Rx) when it detects activity in the Tx transmission line, avoiding the need for software control.

Using the RS2RS as an amplifier extends the length of an installation’s RS-485 bus, which generally does not exceed 1,200 metres. It can be used in installations where there are communication issues due to interference or cabling distances.

Key Features

  • RS-232 / RS-485 bus transducer.
  • RS-485 / RS-485 amplifier.
  • Auto-detection of word speed and length, from 300 to 115,000 bauds.
  • Galvanic insulation, up to 3 kV.
  • 120 … 230 Vac power supply
  • Power, TX and RX LED
  • Assembly. DIN 46277 (EN-50022), 3 DIN 43880 modules

Technical Specifications

AC power supply

RS2RS AC power supply
Nominal voltage120 … 230 V ~ ±10%
Frequency50 / 60 Hz
Consumption0,7 … 2,3 VA

Serial communication

RS2RS Serial communication
Technology / TypeRS-232 / RS-485

User interface

RS2RS User interface
LED3 LEDs (Indication transmission: Tx and Rx – Power supply)

Environmental characteristics

RS2RS Environmental characteristics
Working temperature0 … +50 °C
Storage temperature-10 … +60 °C
Relative humidity (without condensation)25 … 85%
Protection classIP20

Mechanical characteristics

RS2RS Mechanical characteristics
EnvelopeNoryl V0 1550
Weight (kg)0,182
Size (width × height × depth)70 × 106 × 58 mm

Standards

RS2RS Standards
StandardsUNE-EN 61000-6-2, UNE-EN 61000-6-4
Electrical safety, Installation categoryCAT III 300 V (IEC 61010)
Electrical safety, Maximum height (m)2000

Electrical safety

RS2RS Electrical safety
InsulationDouble-insulated electric shock protection class II (IEC 61010-1)

Applications

For any installation that has units with RS-485 communications that need to communicate over an RS-232 connection.

Amplification of the RS-485 bus where the required distance exceeds 1200 metres.

Amplification of RS-485 signals in installations where there are communications problems.

Need more detailed information?

View the official product documentation,
manuals and technical resources.

Visit Circutor Website