Protection and Control

WGBU-70

Residual current relay

Code: P16012

Usefull diam.(mm): 70
IΔn (A): 0,03 … 3 A
Delay: 0,02…1 s
Mounting: Panel background
Download Datasheet

Overview

The WGBU Series is a compact residual current protection system. It is composed of a toroidal transformer with a built-in residual current relay.

Key Features

  • Multi-range electronic relay — Adjustable sensitivity from 0.03 to 3 A.
  • Adjustable trigger delay — Adjustable trigger delay from 0.02 to 1 s.
  • Type A differential protection — High-immunity Type A relay with high-frequency current filtering.
  • True RMS monitoring — Monitoring of residual current using true RMS (TRMS) measurement.
  • Grid connection indication — LED indicator for grid connection status.
  • Pre-alarm and trigger indication — LED flashes every 2 s for leakage between 25 and 50%, every 1 s for 50–75%, and every 0.5 s for leakage exceeding 75% of the selected sensitivity.
  • Residual current trip indication — Permanently lit LED indicates activation of residual current protection.

Technical Specifications

AC power supply

WGBU-70 AC power supply
Nominal voltage110/230 V ~ ±20%
Frequency50/60 Hz

AC power supply, insulation

WGBU-70 AC power supply, insulation
Test voltage (kV)2,5 kV ~

Digital relay outputs

WGBU-70 Digital relay outputs
Nominal voltage250 V ~
Nominal current6 A ~
Resistive load (max.)250 Vac / 8 Aac

Other digital relay outputs

WGBU-70 Other digital relay outputs
Electrical life2 × 10⁵
Insulation voltage250 V ~

Environmental characteristics

WGBU-70 Environmental characteristics
Working temperature-10 … +50 °C
Protection classIP20 (terminals), IP41 (rear panel)

Mechanical characteristics

WGBU-70 Mechanical characteristics
FasteningDIN rail
Weight (kg)0,375
Size (width × height × depth)196 × 110 × 46 mm

Protection

WGBU-70 Protection
Circuit breaker typeContactor or circuit breaker + trigger coil
LED indicationPower supply voltage / Earth leakage tripping / Prealarm
MeasureTrue root mean square (TRMS)

Differential protection

WGBU-70 Differential protection
TransformerBuilt-in, WG series
TypeType A ultra-immunised
Sensitivity (I∆n), A0,03 … 3 (selectable)
Delay time (t∆)0.02 … 5 s (selectable)

Standards

WGBU-70 Standards
StandardsIEC 1008, IEC 255-5, UNE 801-2, UNE 801-3, UNE 801-4, UNE 60730-1

Applications

The WGBU series offers a reliable residual current protection, with simpler cabling and savings in the assembly time. In addition, installation is very simple, thanks to its compact dimensions.

Need more detailed information?

View the official product documentation,
manuals and technical resources.

Visit Circutor Website